Out of stock
The inductive sensor is a rectangular-type proximity sensor designed for reliable detection of metallic objects at a rated operating distance of 4 mm. This robust sensor features a durable PA housing and is well-suited for various industrial applications.
Pepperl+Fuchs offers a comprehensive range of inductive proximity sensors known for their precision and reliability in detecting metallic objects without direct contact. These sensors operate using electromagnetic fields, allowing them to function effectively in a variety of environments, including those with dust, dirt, and moisture. Their compact design and flush installation capability make them ideal for applications where space is limited.
Common applications for inductive proximity sensors include automation systems, material handling, and packaging machinery. They are frequently used in assembly lines to monitor the presence of components, ensuring optimal operation and reducing the risk of machinery jams. Additionally, these sensors are compatible with various connection types, enabling easy integration into existing setups.
| General specifications | ||
| Switching element function | PNP |
|
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 … 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 … 30 V DC | |
| Switching frequency | 0 … 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | less than or equal to 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 … 250 mA | |
| Off-state current | 0 … 0.01 mA typ. 0.1 mA at 25 �C | |
| No-load supply current | less than or equal to 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1640 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Design-impulse-voltage withstand | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated less than or equal to 36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 … 70 �C (-13 … 158 �F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |