The Inductive sensor from Pepperl+Fuchs is designed for reliable object detection in various industrial environments. With a rated operating distance of 15 mm and durable PBT housing, it offers robust performance for flush installation applications.
Inductive proximity sensors are essential components in automation and control systems, widely used for detecting metallic objects without direct contact. These sensors operate on the principle of electromagnetic induction, generating a field that can sense the presence of a metal target within a specified range.
Common applications include automated assembly lines, material handling, and safety interlocks, where precise detection is paramount. The sensors are particularly valued for their durability and resistance to environmental factors, making them suitable for challenging conditions. The flush installation capability allows for seamless integration into machinery and equipment, ensuring optimal performance in tight spaces.
With a two-wire output and DC voltage type, these sensors facilitate straightforward wiring and integration into existing systems, enhancing operational efficiency. Their versatility and reliability make them a preferred choice in manufacturing and processing industries.
| General specifications | ||
| Switching element function | NAMUR, NC | |
| Rated operating distance | 15 mm | |
| Installation | flush | |
| Output polarity | NAMUR | |
| Assured operating distance | 0 … 12.15 mm | |
| Reduction factor rAl | 0.28 | |
| Reduction factor rCu | 0.25 | |
| Reduction factor r304 | 0.75 | |
| Nominal ratings | ||
| Nominal voltage | 8 V | |
| Switching frequency | 0 … 400 Hz | |
| Hysteresis | 1 … 15 typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | yes | |
| Current consumption | ||
| Measuring plate not detected | min. 3 mA | |
| Measuring plate detected | less than or equal to 1 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 3387 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
| Electromagnetic compatibility | NE 21:2007 | |
| Approvals and certificates | ||
| FM approval | ||
| Control drawing | 116-0165F | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated less than or equal to 36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 … 100 �C (-13 … 212 �F) | |
| Storage temperature | -40 … 100 �C (-40 … 212 �F) | |
| Mechanical specifications | ||
| Connection type | terminal compartment | |
| Core cross-section | up to 2.5 mm2 | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Degree of protection | IP68 | |
| General information | ||
| Use in the hazardous area | see instruction manuals | |
| Category | 1G- 2G- 1D | |