The inductive sensor series from Pepperl+Fuchs provides reliable detection of metallic objects without physical contact. These sensors are designed for automation and industrial applications, ensuring precise performance in demanding environments.
Inductive proximity sensors are essential components in various industrial automation applications, offering non-contact detection of metallic objects. Utilizing electromagnetic fields, these sensors function by generating a field that changes when a metal object enters its range, thereby triggering an output signal. This technology eliminates wear and tear associated with mechanical switches, resulting in increased reliability and longevity.
These sensors are commonly employed in manufacturing processes, robotics, and conveyor systems, where precise positioning and object detection are critical. Their robust design enables them to withstand harsh environmental conditions, including dust, moisture, and vibrations, making them suitable for use in manufacturing plants, packaging lines, and assembly stations.
With a wide range of sensing distances and configurations, inductive sensors provide flexibility for various applications. Their ability to operate without direct contact with the target object enhances safety and efficiency in automated systems, contributing to streamlined operations in modern industry.
| General specifications | ||
| Switching element function | NAMUR, NC | |
| Rated operating distance | 2 mm | |
| Installation | flush | |
| Output polarity | NAMUR | |
| Assured operating distance | 0 … 1.62 mm | |
| Reduction factor rAl | 0.23 | |
| Reduction factor rCu | 0.21 | |
| Reduction factor r304 | 0.7 | |
| Nominal ratings | ||
| Nominal voltage | 8.2 V (Ri approx. 1 kOm) | |
| Operating voltage | 5 … 25 V | |
| Switching frequency | 0 … 1000 Hz | |
| Hysteresis | 1 … 10 typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | yes | |
| Suitable for 2:1 technology | yes , Reverse polarity protection diode not required | |
| Current consumption | ||
| Measuring plate not detected | greater or equal 2.2 mA | |
| Measuring plate detected | less than or equal to 1 mA | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 2698 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
| Electromagnetic compatibility | NE 21:2007 | |
| Approvals and certificates | ||
| FM approval | ||
| Control drawing | 116-0165F | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated less than or equal to 36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 … 100 °C (-13 … 212 °F) | |
| Storage temperature | -40 … 100 °C (-40 … 212 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M12 x 1 , 4-pin | |
| Housing material | Stainless steel 1.4305 / AISI 303 | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP66 / IP67 | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| Use in the hazardous area | see instruction manuals | |
| Category | 1G- 2G- 1D | |