Pepperl+Fuchs Z965

Zener Barrier
SKU: Z965
0.00

Out of stock

One click request

The Zener Barrier is a robust 2-channel AC version designed for intrinsic safety in hazardous environments. With a working voltage of 13 V at 10 µA and maximum series resistance of 115 Ω, it ensures reliable operation in critical applications.

All description
Manufacturer: Pepperl+Fuchs
Description:

The Zener Barrier product family is essential for ensuring intrinsic safety in electrical systems operating in potentially explosive atmospheres. These barriers provide a reliable means of protecting equipment and personnel by limiting the energy available in hazardous areas. They are particularly useful in applications where instrumentation must interface with field devices located in zones classified as hazardous due to the presence of flammable gases or dust.

These barriers are designed for DIN rail mounting and utilize a star connection topology, allowing for flexible installation configurations. The maximum fuse rating of 50 mA further enhances the safety and reliability of the system, ensuring that any overcurrent conditions are effectively managed. Typical applications include use in process automation, oil and gas industries, and any systems requiring stringent safety measures to prevent ignition in explosive atmospheres.

Core cross-section max. 2 x 2.5 … mm2
Mass approx. 150 g
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Nominal resistance 100 Ω
EU-type examination certificate BAS 01 ATEX 7005
Certificate TV 99 ATEX 1484 X
IECEx approval IECEx BAS 09.0142
IECEx BAS 17.0091X
Construction type modular terminal housing , see system description
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Degree of protection IP20
Series resistance min. 98 Ω
Dimensions 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch)
Fuse rating 50 mA
Connection screw terminals
Relative humidity max. 75 % , without condensation
Connection terminals 5, 6; 7, 8
Degree of protection IEC 60529
Type AC version
Series resistance max. 115 Ω
Storage temperature -25 … 70 °C (-13 … 158 °F)
Ambient temperature -20 … 60 °C (-4 … 140 °F)
Connection terminals 1, 2; 3, 4
Reviews
Leave feedback on the goods

Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.

Leave feedback

Thank you for your feedback. In order to leave your feedback, simply fill out the form below.

Thank you for your feedback. In order to leave your feedback, simply fill out the form below. “Pepperl+Fuchs Z965”

Your email address will not be published. Required fields are marked *

Other products categories