Pepperl+Fuchs HiC2441

SMART Universal Barrier
SKU: HiC2441
0.00

Out of stock

One click request

The SMART Universal Barrier is a 1-channel isolated barrier designed for versatile applications in hazardous environments. It supports both analog and digital inputs and outputs with a 24 V DC supply, ensuring efficient operation without the need for configuration.

All description
Manufacturer: Pepperl+Fuchs
Description:

The SMART Universal Barrier from Pepperl+Fuchs is an advanced solution for intrinsic safety applications, particularly in industrial settings where hazardous conditions may persist. This device offers a robust 3-way isolation feature, making it suitable for connecting field devices directly to control systems while ensuring protection against electrical faults. Its capability to handle both analog and digital signals enhances its versatility, allowing it to be deployed in various monitoring and control scenarios.

Designed to operate with a bus-powered 24 V DC supply, the barrier facilitates seamless integration into existing systems without the need for extensive configuration, thanks to its self-adapting functionality. The product supports HART transparency, enabling two-way communication with smart field devices, which is essential for advanced diagnostics and process automation. Additionally, the device is characterized by low power dissipation and compliance with safety standards, achieving up to SIL 2 according to IEC 61508, making it a reliable choice for safety-critical applications.

Ambient temperature -40 … 70 °C (-40 … 158 °F)
Observe the temperature range limited by derating, see section derating.
Field circuit SL2: 5a(+), 5b(-)
Signal type Universal
Frequency range HART: bandwidth by 0.5 Vpp signal and/or 1 mApp signal 950 … 2500 Hz (analog input, analog output)
Input EN 60947-5-6:2000
Ripple 20 mV rms
Power consumption 700 mW
Voltage 12 … 30 V
UL approval E106378
Protection against electrical shock IEC 61010-1:2010
Equipment SL2: 5a(+), 1a(-)
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Deviation at 20 °C (68 °F)
�20 andmicro;A incl. linearity, hysteresis and supply fluctuations at 4 … 20 mA (analog input, analog output)
�60 andmicro;A incl. linearity, hysteresis and supply fluctuations at 0 … 45 mA (digital output)
Signal 0.1 … 9 mA
Supply voltage min. 16 V at 20 mA (2-wire SMART transmitter)
Control circuit SL1: 8a(+), 7a(-)
Switching frequency 500 Hz with 50 % duty cycle (digital input, NAMUR sensor)
5 Hz (digital input, dry contact)
20 Hz (digital output)
Field circuit SL2: 5a(+), 5b(-)
Voltage 1-signal: 19 … 30 V DC
0-signal: 0 … 5 V DC
Equipment SL2: 5a(+), 1b(-)
Suitable field devices I/P converters (positioner), on-site-displays
Load 0 … 650 andOmega;
Line fault detection > 100 kandOmega; at max. 30 V, with field wiring open
Coding pin 1 and 4 trimmed
For further information see system description.
Suitable field devices NAMUR sensors according to IEC/EN 60947-5-6, dry contacts
Rated current 30 mA
Drive capability 12 V / 40 mA at 300 andOmega; load
Certificate TV 14 ATEX 153523 X
Signal 0/4 … 20 mA , sink mode , working voltage 15 … 30 V
Ripple 10 %
Current limit 45 mA
Suitable field devices solenoid valves, acoustic or visual alarms
Signal 0/4 … 20 mA
Safety Integrity Level (SIL) SIL 2
Voltage 13 V at 20 mA
Mounting on Termination Board
EU-Type Examination Certificate TV 14 ATEX 153522 X
Voltage drop approx. 4 V (current source)
Connection SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Equipment SL2: 5a(+), 5b(-)
Power dissipation 1.1 W at 24 V, 300 andOmega; load (digital output)
Field circuit SL2: 5a(+), 1a(-) (NAMUR sensor)
SL2: 5a(+), 5b(-) (dry contact)
Signal 0/4 … 20 mA , limited to approx. 40 mA (depends on control system) , reverse polarity protected
Storage temperature -40 … 85 °C (-40 … 185 °F)
Settling time 20 ms (analog input, analog output)
1 ms (digital input, NAMUR sensor)
Suitable field devices 2-wire SMART transmitters, current sources
Control circuit SL1: 8a(+), 7a(-)
Voltage 13 … 30 V
Electromagnetic compatibility NE 21:2011
Signal 0.1 … 9 mA , sink mode
Open loop voltage approx. 22 V
Field circuit SL2: 5a(+), 5b(-) (2-wire SMART transmitter)
SL2: 5a(+), 1b(-) (2-wire SMART transmitter with current source)
Open loop voltage approx. 10 V DC , 1 kandOmega; series resistance
Degree of protection IP20
Rated voltage 19 … 30 V DC via Termination Board
Degree of protection IEC 60529:2001
Voltage 15 … 30 V
Relative humidity 95 % non-condensing
Ripple 20 mV rms
Mass approx. 100 g
Control circuit SL1: 8a(+), 7a(-)
Control circuit SL1: 8a(+), 7a(-)
Control/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Internal resistor min. 240 andOmega;
Signal 0/4 … 20 mA
Current 1-signal: 0 … 45 mA, depending on the output load
0-signal: < 0.1 mA, independent of the output load
Dimensions 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Reaction time 5 ms , turn-on/turn-off time (digital output)
Reviews
Leave feedback on the goods

Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.

Leave feedback

Thank you for your feedback. In order to leave your feedback, simply fill out the form below.

Thank you for your feedback. In order to leave your feedback, simply fill out the form below. “Pepperl+Fuchs HiC2441”

Your email address will not be published. Required fields are marked *

Other products categories