The Solenoid Driver is a 1-channel isolated barrier designed for robust applications requiring 24 V DC supply, either bus or loop powered. It delivers an output of 45 mA at 12 V DC and features line fault transparency (LFT) for enhanced reliability.
The Solenoid Driver is part of a specialized family of intrinsic safety barriers, providing critical isolation in hazardous environments. These barriers are essential for ensuring that the electrical signals used for controlling solenoids do not pose a risk of igniting flammable gases or dust present in industrial settings. By converting high-voltage signals to lower voltages suitable for field devices, they maintain safety while facilitating efficient operation.
This device is particularly suited for applications requiring precise control in industries such as oil and gas, chemical processing, and manufacturing. With features including test pulse immunity and compliance with SIL 3 according to IEC/EN 61508, the Solenoid Driver offers a high level of reliability and safety. Its line fault transparency ensures that any faults in the system are easily detectable, further enhancing system integrity in critical applications.
| Signal type | Digital Output | |
| Safety Integrity Level (SIL) | SIL 3 | |
| Systematic capability (SC) | SC 3 | |
| Connection | SL1: 1a, 1b(-); 2a, 2b(+) | |
| Rated voltage | 19 … 30 V bus powered via Termination Board 19 … 30 V loop powered via input , reverse polarity protected |
|
| Input current | 75 mA at 24 V, 270 Ω load | |
| Power dissipation | 1.3 W at 24 V, 270 Ω load | |
| Connection side | control side | |
| Connection | SL1: 7a(-), 9a(-); 8a(+), 10a(+) | |
| Test pulse length | max. 2 ms from DO card | |
| Signal level | loop powered 1-signal: 19 … 30 V DC 0-signal: 0 … 5 V DC bus powered 1-signal: 15 … 30 V DC (current limited at 5 mA) 0-signal: 0 … 5 V DC |
|
| Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ‰§ 36 mA (minimum load current DO card) |
|
| Inrush current | < 200 mA , 10 ms loop powered | |
| Connection side | field side | |
| Connection | SL2: 5a(+), 5b(-) | |
| Internal resistor | approx. 240 Ω | |
| Current | typ. 45 mA | |
| Voltage | ‰§ 12 V | |
| Current limit | 50 mA | |
| Open loop voltage | typ. 24.6 V | |
| Load | nominal 0.05 … 18 kΩ | |
| Switching frequency | max. 10 Hz | |
| Energized/De-energized delay | 20 ms / 5 ms | |
| Line fault detection | ||
| Short-circuit | < 25 Ω | |
| Open-circuit | > 50 kΩ | |
| Test current | < 500 µA | |
| Connection | SL1: 6b | |
| Output type | open collector transistor (internal fault bus) | |
| Output/other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Display elements | LEDs | |
| Control elements | DIP switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Electromagnetic compatibility | NE 21:2017 , IEC/EN 61326-3-2:2018 For further information see system description. |
|
| Degree of protection | IEC 60529:2013 | |
| Protection against electrical shock | UL 61010-1:2012 | |
| Ambient temperature | -40 … 70 °C (-40 … 158 °F) | |
| Degree of protection | IP20 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D) | |
| Mounting | on termination board | |
| Coding | pin 1 and 4 trimmed For further information see system description. |
|
| EU-type examination certificate | FIDI 21 ATEX 0069X | |
| Marking | II 3(1)G Ex nC ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
| Output | Ex ia | |
| Voltage | 26 V | |
| Current | 110 mA | |
| Power | 715 mW | |
| Supply | ||
| Maximum safe voltage | 60 V (Attention! The rated voltage can be lower.) | |
| Input | ||
| Maximum safe voltage | 60 V (Attention! The rated voltage can be lower.) | |
| Galvanic isolation | ||
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms | |
| Directive conformity | ||
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019 | |
| FM approval | FM 17 US 0111 X , FM 17 CA 0057 X | |
| Control drawing | 116-0442 | |
| UL approval | E106378 | |
| Control drawing | 116-0447A (cULus) | |
| IECEx approval | ||
| IECEx certificate | IECEx EXA 17.0009X | |
| IECEx marking | Ex nC ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I |
|
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |
| ECLASS 13.0 | 27210101 | |
| ECLASS 12.0 | 27210190 | |
| ECLASS 11.0 | 27210190 | |
| ECLASS 10.0.1 | 27210190 | |
| ECLASS 9.0 | 27210190 | |
| ECLASS 8.0 | 27210190 | |
| ECLASS 5.1 | 27210121 | |
| ETIM 9.0 | EC001485 | |
| ETIM 8.0 | EC001485 | |
| ETIM 7.0 | EC001485 | |
| ETIM 6.0 | EC001485 | |
| ETIM 5.0 | EC001485 | |
| UNSPSC 12.1 | 39121008 | |