Out of stock
The Termination Board is designed to facilitate seamless integration within the Schneider and Foxboro FBM series systems. It efficiently accommodates up to eight modules and is compatible with various 8-channel cards, making it a versatile component in process automation.
The Termination Board serves as a critical system component in the integration of various modules within hazardous and non-hazardous environments. Designed for use with the Schneider and Foxboro FBM series, this board supports up to eight modules, thereby enhancing the operational capabilities of process control systems. Its configuration allows for the use of multiple channel cards, providing flexibility in applications ranging from analog input and output to universal input/output functionalities.
This product is engineered for robust performance in hazardous areas, featuring screw terminals that ensure secure connections. The non-hazardous side is equipped with a 25-pin Sub-D connector, allowing for easy interfacing with external devices. With a 24 V DC power supply requirement, the Termination Board is well-suited for environments where safety and reliability are paramount, such as chemical processing, oil and gas, and other industrial sectors.
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered |
| Material | housing: polycarbonate, 10 % glass fiber reinforced |
| Degree of protection | IEC 60529:2001 |
| Output type | volt-free contact |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Ripple | ≤ 10 % |
| IECEx approval | IECEx CES 06.0003 |
| Supply | Redundancy available. The supply for the isolators is decoupled, monitored and fused. |
| Nominal voltage | 24 V DC , in consideration of rated voltage of used isolators |
| Connection | X20: terminals 3, 5 (+); 4, 6 (-) |
| Core cross-section | screw terminals: 0.25 … 1.5 mm2 (24 … 12 AWG) |
| Display elements | LED PWR1 (termination board power supply), green LED LED PWR2 (termination board power supply), green LED LED FAULT (fault indication), red LED – LED lits: module failure – LED flashes: power supply failure |
| Degree of protection | IP20 |
| Mass | approx. 380 g |
| Storage temperature | -40 … 70 °C (-40 … 158 °F) |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| Dimensions | 108 x 200 x 163 mm (4.25 x 7.9 x 6.42 inch) , height including module assembly |
| Contact loading | 30 V DC, 1 A |
| EU-type examination certificate | CESI 06 ATEX 022 |
| Fusing | 2 A , in each case for 8 modules |
| Connection | X20: terminals 1, 2 |
| Reverse polarity protection | yes |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Electromagnetic compatibility | NE 21:2017 For further information see system description. |
| Designation | optional accessories: – HART multiplexer master HiDMux2700 – label carrier HiALC-Hi*TB-SET-1** |
| Power dissipation | ≤ 500 mW , without modules |
Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.
Thank you for your feedback. In order to leave your feedback, simply fill out the form below.