The Termination Board is designed to accommodate 16 modules with a 24 V DC supply. It supports various signal types including Digital Inputs, Digital Outputs, Analog Inputs, Temperature Inputs, and Analog Outputs. The board features distinct screw terminals for hazardous and non-hazardous areas, facilitating safe and efficient installation.
The Termination Board is a critical component in the Pepperl+Fuchs family of Intrinsic Safety Barriers, specifically engineered for applications in hazardous environments. These barriers are vital for ensuring safety in industrial settings where flammable gases or combustible dust may be present. The Termination Board allows for the secure connection of up to 16 modules, which can handle multiple signal types such as Digital Inputs (DI), Digital Outputs (DO), Analog Inputs (AI), Temperature Inputs (TI), and Analog Outputs (AO).
With dedicated screw terminals for both hazardous and non-hazardous areas, the Termination Board ensures clear identification and ease of installation. The blue screw terminals are designated for hazardous areas, while the black terminals are used in non-hazardous environments. This design not only enhances safety but also simplifies the wiring process, making it an essential solution for applications in process automation, instrumentation, and other industrial control systems.
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered |
| Dimensions | 216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) , height including module assembly |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Display elements | LED PWR1 (termination board power supply), green LED LED PWR2 (termination board power supply), green LED LED FAULT (fault indication), red LED – LED lits: module failure – LED flashes: power supply failure |
| Output type | volt-free contact |
| Fusing | 4 A , in each case for 16 modules |
| EU-Type Examination Certificate | CESI 06 ATEX 022 |
| Power dissipation | 500 mW , without modules |
| Electromagnetic compatibility | NE 21:2017 For further information see system description. |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Connection | X20: terminals 1, 2 |
| Degree of protection | IP20 |
| Core cross-section | screw terminals: 0.25 … 1.5 mm2 (24 … 12 AWG) |
| Nominal voltage | 24 V DC , in consideration of rated voltage of used isolators |
| Connection | X20: terminals 3, 5 (+); 4, 6 (-) |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| Ripple | 10 % |
| Storage temperature | -40 … 70 °C (-40 … 158 °F) |
| Material | housing: polycarbonate, 10 % glass fiber reinforced |
| Degree of protection | IEC 60529:2001 |
| Certificate | DEMKO 18 ATEX 2116 X |
| Reverse polarity protection | yes |
| Mass | approx. 870 g |
| Supply | Redundancy available. The supply for the isolators is decoupled, monitored and fused. |
| Designation | optional accessories: – HART communication board HiATB01-HART-4X8-Y1 – HART multiplexer master HiDMux2700 – HART connection cable HiACA-UNI-FLK34-*M* – label carrier HiALC-Hi*TB-SET-1** |
| Contact loading | 30 V DC, 1 A |
Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.
Thank you for your feedback. In order to leave your feedback, simply fill out the form below.