Out of stock
This termination board is designed for use with the Yokogawa CENTUM VP system, facilitating the integration of a 16-channel analog input card. It supports up to 16 modules and is equipped with spring terminals for hazardous areas.
The Termination Board is an integral component within the Pepperl+Fuchs family of Intrinsic Safety Barriers, specifically engineered for use in process automation applications involving hazardous environments. This board serves as a critical interface between analog input modules and control systems, ensuring safe and reliable operation in sectors such as oil and gas, chemical processing, and pharmaceuticals.
Designed for compatibility with the Yokogawa CENTUM VP system, the Termination Board supports a 16-channel analog input configuration, allowing for the connection of multiple sensors or devices simultaneously. Its robust construction includes spring terminals for the hazardous area, providing secure connections while maintaining compliance with safety regulations. The board is powered by a 24 V DC supply, making it suitable for a wide range of industrial applications where intrinsic safety is paramount.
| Degree of protection | IEC 60529:2001 |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| Contact loading | 30 V DC , 1 A |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Storage temperature | -40 … 70 °C (-40 … 158 °F) |
| Fusing | 4 A , in each case for 16 modules |
| Reverse polarity protection | yes |
| IECEx approval | IECEx CES 06.0003 |
| Material | housing: polycarbonate |
| Nominal voltage | 24 V DC , in consideration of rated voltage of used isolators |
| Ripple | ≤ 10 % |
| Electromagnetic compatibility | NE 21:2012 For further information see system description. |
| Mass | approx. 650 g |
| Power dissipation | ≤ 500 mW , without modules |
| Core cross-section | spring terminals: rigid: 0.2 … 2.5 mm2 flexible: 0.25 … 1.5 mm2 |
| Supply | Redundancy available. The supply for the isolators is decoupled, monitored and fused. |
| Display elements | LEDs PWR ON (Termination Board power supply) – LED power supply I, green LED – LED power supply II, green LED LED FAULT (fault indication), red LED – LED lits: module failure – LED flashes: power supply failure |
| Dimensions | 240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) , height including module assembly |
| EU-Type Examination Certificate | CESI 06 ATEX 022 |
| Degree of protection | IP20 |
| Output type | volt-free contact |
Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.
Thank you for your feedback. In order to leave your feedback, simply fill out the form below.