Out of stock
The SMART Transmitter Power Supply provides reliable and safe power for 2-wire SMART transmitters and current sources in hazardous environments. It operates on a 24 V DC supply and offers dual output capabilities for effective signal management.
The SMART Transmitter Power Supply is an essential component in the realm of intrinsic safety barriers, designed to ensure safe operation in hazardous areas. This 2-channel isolated barrier is engineered to supply power to 2-wire SMART transmitters and current sources, effectively isolating the field devices from the control system. This functionality is crucial in environments where safety and efficiency are paramount.
One of the key features of this product is its ability to function as a signal splitter, allowing one input to provide two outputs. This dual output configuration supports a current range of 4 mA to 20 mA, making it suitable for various industrial applications. Additionally, the device incorporates line fault detection (LFD) and meets safety requirements up to SIL 2 according to IEC 61508 standards, ensuring compliance with stringent safety regulations.
| Coding | pin 1 and 3 trimmed For further information see system description. |
| Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
| Connection | SL1: 8a(+), 7a(-); 10a(+), 9a(-) |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Output type | open collector transistor (common to both channels) fault bus signal, collective error message |
| Relative humidity | 5 … 90 %, non-condensing up to 35 °C (95 °F) |
| Rated voltage | 20.4 … 30 V DC bus powered via Termination Board |
| Connection side | field side |
| Calibrated accuracy | < � 0.1 % of full-scale value |
| Communication | pass-through of HART signal to safe area The current sink terminals 4, 7 and 5, 6 do not pass the HART signal to safe area. |
| Frequency range | communication channel: 0.5 … 40 kHz within 3 db, (-6 db at 100 kHz), Tx to output and output to Tx, suitable for use with SMART transmitters using HART or similar protocol |
| Display elements | LEDs |
| Degree of protection | IP20 |
| Mass | approx. 140 g |
| Signal level | no fault: 1 mA … 23.5 mA input current fault detection: < 0.2 mA or > 24 mA input current |
| Output/Output | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
| Electromagnetic compatibility | NE 21:2006 For further information see system description. |
| Input current | 4 … 20 mA , current limit 26 mA |
| EU-type examination certificate | CESI 02 ATEX 086 |
| Output | sink mode from external supply |
| Rated current | 40 mA at 24 V, 20 mA output (per channel) |
| Signal type | Analog input |
| Safety Integrity Level (SIL) | SIL 2 |
| Connection | SL1: 6b |
| Influence of temperature | < � 0.01 %/ K |
| Labeling | space for labeling at the front |
| Ripple | 10 mV eff |
| Degree of protection | IEC 60529 |
| Output/power supply | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
| IECEx approval | IECEx TUN 04.0012 |
| Connection | SL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-) |
| Connection side | control side |
| Linearity | < � 0.05 % of full-scale value |
| Output signal | 4 … 20 mA , current limit 24 mA |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| Mounting | on Termination Board |
| Voltage | working voltage 7 … 30 V |
| Power dissipation | 1.05 W at 20 mA and 24 V external from PCS or PLC (per channel) |
| Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
| Input resistance | 40 Ω , for current source |
| Certificate | PF 11 CERT 2109 X |
| Voltage | min. 15.5 V at 20 mA |
| Response time | 70 ms , 10 … 90 % step change |