Out of stock
The Temperature Repeater is a 1-channel isolated barrier designed for precise temperature measurement and control in hazardous environments. It supports a 24 V DC supply and is compatible with various resistance and RTD inputs, ensuring accurate readings and reliable performance.
The Temperature Repeater belongs to the Pepperl+Fuchs family of intrinsic safety barriers, which are essential in applications where safety and reliability are paramount, particularly in explosive atmospheres. This device is engineered to convert temperature signals from resistance temperature detectors (RTDs) and resistance inputs into isolated, standardized outputs. Its compact housing design facilitates integration within various industrial setups while adhering to stringent space requirements.
Common applications for the Temperature Repeater include monitoring and controlling temperature in process industries, chemical plants, and other environments where hazardous materials may be present. With an accuracy of 0.1%, it ensures precise measurements, while features such as line fault detection for Pt100 inputs enhance system safety. Additionally, the device meets up to SIL 2 standards according to IEC 61508, making it suitable for use in safety-critical applications.
| Connection side | control side |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| Connection | terminals 1, 2, 3, 4 |
| Display elements | LED |
| Degree of protection | IEC 60529:2001 |
| Labeling | space for labeling at the front |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Degree of protection | IP20 |
| Available voltage | 0 … 4.2 V |
| Ripple | within the supply tolerance |
| Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
| Control elements | DIP-switch |
| Connection side | field side |
| IECEx approval | IECEx BAS 10.0024 IECEx BAS 10.0025X |
| Protection against electrical shock | UL 61010-1 |
| Available voltage | 9 V |
| Output/power supply | functional insulation, rated insulation voltage 50 V AC |
| Connection | Power Rail or terminals 9+, 10- |
| Configuration | via DIP switches |
| Lead resistance | 10 % of resistance value |
| Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
| Mass | approx. 100 g |
| Deviation | Im 1 mA: ±0.1 % of Rm or ± 0.1 andOmega; (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ± 1 % of Rm or 1 andOmega; (the larger value is applicable). |
| Signal type | Analog input |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Safety Integrity Level (SIL) | SIL 2 |
| Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 |
| Electromagnetic compatibility | NE 21:2011 |
| Certificate | BASEEFA 10 ATEX 0062X |
| Line fault detection | 8 nA |
| Accuracy | 0.1 % |
| Rated current | < 20 mA |
| Power consumption | 0.35 W (24 V and 1 mA sense current) |
| Optional accessories | – power feed module KFD2-EB2(.R4A.B)(.SP) – universal power rail UPR-03(-M)(-S) – profile rail K-DUCT-BU(-UPR-03) |
| Fault signal | < 10 andOmega; or > 400 andOmega;, depending on lead disconnected (measuring current 1 mA) > 400 andOmega;, terminal 3 lead disconnected in 2-/4-wire (measuring current 0.3 mA) |
| Line fault detection | yes , at Pt100 |
| Rise time | signal response time 2 ms (10 … 90 %) response to application of Im: Rm > 50 andOmega; and Im < 5mA: < 5ms response to application of Im: Rm > 30 andOmega; and Im < 5mA: < 10ms response to application of Im: Rm > 18 andOmega; and Im < 5mA: < 20ms |
| Connection | spring terminals |
| Connection | terminals 5-, 7-, 6+, 8+ |
| Transmission range | 0 … 10 mA |
| Rated voltage | 19 … 30 V DC |
| EU-Type Examination Certificate | BASEEFA 10 ATEX 0061 |
Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.
Thank you for your feedback. In order to leave your feedback, simply fill out the form below.