Pepperl+Fuchs KCD2-RR2-Ex1

Resistance Repeater
SKU: KCD2-RR2-Ex1
0.00

Out of stock

One click request

The Resistance Repeater is a sophisticated 1-channel isolated barrier designed for use in intrinsic safety applications. With a 24 V DC supply and compatibility with various resistance and RTD inputs, it ensures high accuracy and reliability in measurement tasks.

All description
Manufacturer: Pepperl+Fuchs
Description:

The Resistance Repeater is a critical component in the Pepperl+Fuchs family of intrinsic safety barriers, designed to enhance the safety and reliability of measurement systems in hazardous environments. This device is particularly useful for applications involving resistance and RTD sensors, such as Pt100, Pt500, and Pt1000, making it ideal for temperature measurement and process control in various industrial settings.

With an accuracy of 0.1%, the Resistance Repeater ensures precise data transmission, which is crucial for maintaining operational integrity and safety. The inclusion of line fault detection (LFD) for Pt100 sensors further enhances its reliability, providing operators with real-time monitoring capabilities. The compact housing, with a width of only 12.5 mm, allows for efficient use of panel space without compromising on performance, making it a valuable addition to systems that adhere to safety integrity levels (SIL 2) according to IEC 61508 standards.

Rated voltage 19 … 30 V DC
Available voltage 7 V
Current 0 … 10 mA
Mass approx. 100 g
Line fault detection yes , at Pt100
Output/power supply functional insulation, rated insulation voltage 50 V AC
Electromagnetic compatibility NE 21:2017
EN IEC 61326-3-2:2018
Fault signal field voltage < 150 mV or > 4 V, depending on lead disconnected
Available voltage 0 … 4.2 V
Accuracy 0.1 %
Control elements DIP-switch
Protection against electrical shock UL 61010-1:2012
UL approval E106378
Lead resistance ≤ 10 % of resistance value
Degree of protection IEC 60529:2001
Certificate BASEEFA 10 ATEX 0062X
Rated current < 28 mA
Reverse polarity protection for I < 10 mA or U < 20 V
Degree of protection IP20
EU-type examination certificate BASEEFA 10 ATEX 0061X
Power consumption 0.35 W (24 V and 1 mA sense current), 0.85 W (30 V and 10 mA sense current)
Ripple within the supply tolerance
Connection side control side
Line fault detection < 30 nA
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories – power feed module KFD2-EB2(.R4A.B)(.SP)
– universal power rail UPR-03(-M)(-S)
– profile rail K-DUCT-BU(-UPR-03)
– insertion bridge EBP 2- 5
Connection Power Rail or terminals 9+, 10-
Connection terminals 5-, 7-, 6+, 8+
Settling time ≤ 5 ms
Display elements LED
Connection screw terminals
Rise time/fall time ≤ 2 ms (10 … 90%)
Safety Integrity Level (SIL) SIL 2
Labeling space for labeling at the front
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Connection terminals 1, 2, 3, 4
Configuration via DIP switches
Connection side field side
Deviation Im ≥ 1 mA: �0.1 % of Rm or � 0.1 Ω (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: � 1 % of Rm or 1 Ω (the larger value is applicable).
Signal type Analog input
Transmission range 0 … 10 mA
Ambient temperature -40 … 70 °C (-40 … 158 °F)
Dimensions 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Reviews
Leave feedback on the goods

Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.

Leave feedback

Thank you for your feedback. In order to leave your feedback, simply fill out the form below.

Thank you for your feedback. In order to leave your feedback, simply fill out the form below. “Pepperl+Fuchs KCD2-RR2-Ex1”

Your email address will not be published. Required fields are marked *

Other products categories