The Switch Amplifier is a versatile 2-channel signal conditioner designed for reliable signal processing in hazardous environments. It accepts dry contact or NAMUR inputs and provides a relay contact output, making it suitable for various applications.
The Switch Amplifier from Pepperl+Fuchs is part of a comprehensive family of intrinsic safety barriers, engineered to ensure safe signal transmission in explosive atmospheres. This product is designed to handle various input types, accommodating both dry contact switches and NAMUR sensors, which are commonly used in industrial automation and process control systems.
With a compact housing width of just 12.5 mm, the Switch Amplifier maximizes space efficiency in control panels while delivering reliable performance. It operates on a 24 V DC supply, ensuring compatibility with standard power rail systems. The built-in line fault detection (LFD) feature enhances system reliability by monitoring for potential faults in the signal path, thus maintaining operational integrity even in challenging environments. The device is certified for up to SIL 2 according to IEC 61508, making it suitable for safety-critical applications.
| Pulse/Pause ratio | min. 20 ms / min. 20 ms |
| Output II | signal ; relay |
| Ripple | 10 % |
| Degree of protection | IP20 |
| Mechanical life | 107 switching cycles |
| Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
| Connection | screw terminals |
| Power consumption | 600 mW |
| Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
| Rated voltage | 19 … 30 V DC |
| Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
| Output I | signal ; relay |
| Mass | approx. 100 g |
| Line fault detection | breakage I 0.1 mA , short-circuit I 6.5 mA |
| Output/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
| Input/input | Basic insulation according to EN 50178, rated insulation voltage 300 Veff |
| Switching frequency | 10 Hz |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Control elements | DIP-switch |
| Electromagnetic compatibility | NE 21:2006 |
| Contact loading | 253 V AC/2 A/cos andphi; > 0.7; 126.5 V AC/4 A/cos andphi; > 0.7; 30 V DC/2 A resistive load |
| Labeling | space for labeling at the front |
| Display elements | LEDs |
| Degree of protection | IEC 60529 |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| Connection side | control side |
| Connection | Power Rail or terminals 9+, 10- |
| Signal type | Digital Input |
| Connection | terminals 1+, 2-; 3+, 4- |
| Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
| Minimum switch current | 2 mA / 24 V DC |
| Safety Integrity Level (SIL) | SIL 2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Connection side | field side |
| Connection | terminals 5, 6; 7, 8 |
| Configuration | via DIP switches |
| Rated current | 30 mA |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Output/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
| Power dissipation | 600 mW |
| Energized/De-energized delay | 20 ms / 20 ms |
| Switching point/switching hysteresis | 1.2 … 2.1 mA / approx. 0.2 mA |