Out of stock
The RTD Converter is a high-performance signal conditioner designed for precise temperature measurement. It accepts 2- or 3-wire Pt100 RTD inputs and provides a standard output of 4 mA to 20 mA with selectable temperature linearization.
The RTD Converter is part of a sophisticated family of intrinsic safety barriers that ensure safe and accurate temperature monitoring in hazardous environments. This 1-channel signal conditioner is powered by a 24 V DC supply and is loop powered, making it ideal for integration into existing systems without the need for additional power sources.
Common applications for the RTD Converter include industrial automation, process control, and environmental monitoring, where reliable temperature measurements are critical. The device features DIP switch selectable ranges, allowing for flexible configuration to meet specific application requirements. Additionally, the built-in sensor breakage detection enhances system reliability by providing immediate alerts in the event of sensor failure, ensuring continuous operation and safety.
| Degree of protection | IEC 60529 |
| Input/Output | safe isolation acc. to DIN VDE 0106, rated insulation voltage 253 Veff |
| Mass | approx. 150 g |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Measurement range | span without linearization 25 … 800 °C (77 … 1472 °F)/ with linearisation 25 … 375 °C (77 … 707 °F) zero point without linearization -200 … 400 °C (-328 … 752 °F)/ with linearisation -30 … 375 °C (-22 … 707 °F) span and zero point adjustable |
| Insulation coordination | EN 50178 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Rated voltage | 12 … 35 V DC loop powered |
| Rise time | 250 ms |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| Degree of protection | IP20 |
| Fault signal | sensor burnout: upscaling 22 mA , limited to 35 mA |
| Power dissipation | 0.4 W |
| Control elements | DIP-switch rotary switch |
| Connection | screw terminals |
| Configuration | via DIP switches via rotary switch |
| Connection | terminals 1, 2-, 3+ suitable for Pt100, 2- and 3-wire connection |
| Measuring current | approx. 1 mA |
| Connection side | control side |
| Current output | 4 … 20 mA , limited to 35 mA |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
| Galvanic isolation | EN 50178 |
| Signal type | Analog input |
| Lead resistance | max. 100 andOmega; per line |
| Load | (U -12 V) / 0.02 A |
| Connection side | field side |
| Labeling | space for labeling at the front |
| Connection | terminals 9+, 8- |