Out of stock
-
Interface for Power Rail
-
Supply current le- 4 A
The Power Feed Module is a crucial component within the Pepperl+Fuchs Intrinsic Safety Barriers family, designed to facilitate safe and reliable power distribution in hazardous environments. These modules ensure that electrical equipment operates safely in areas where flammable gases or dust may be present, adhering to strict safety standards.
This module serves as an interface for a power rail, delivering a supply current of up to 4 A. Such specifications make it suitable for a variety of applications, including industrial automation, process control, and other safety-critical systems. The design is optimized for seamless integration with other intrinsic safety devices, ensuring that users can maintain operational efficiency while prioritizing safety.
|
Labeling |
space for labeling at the front |
|
Control elements |
DIP-switch |
|
Certificate |
TV 00 ATEX 1618 X |
|
Ambient temperature |
-20 … 60 °C (-4 … 140 °F) |
|
Connection |
Power Rail |
|
Power dissipation |
1 W |
|
Supplementary information |
Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
|
Degree of protection |
IP20 |
|
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
|
Connection |
screw terminals |
|
Configuration |
via DIP switches |
|
Optional accessories |
– universal power rail UPR-03(-M)(-S) – universal power rail UPR-05(-S) – profile rail K-DUCT-GY(-UPR-03) – profile rail K-DUCT-GY(-UPR-05) – profile rail K-DUCT-BU(-UPR-03) – profile rail K-DUCT-BU(-UPR-05) |
|
Output voltage |
24 V DC |
|
Contact loading |
30 V AC/ 2 A / cos andphi; 0.7 ; 40 V DC/ 2 A |
|
Connection |
terminals 11+, 12- terminals 8+, 9- |
|
Display elements |
LEDs |
|
Electromagnetic compatibility |
NE 21:2006 |
|
Degree of protection |
IEC 60529:2001 |
|
Energized/De-energized delay |
approx. 20 ms / approx. 20 ms |
|
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
|
Fault signal |
relay output: NO contact |
|
Mass |
approx. 100 g |
|
Fusing |
5 A recommended maximum utilization of the fuse: 80 % |
|
Rated voltage |
20 … 30 V DC The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded. |
|
IECEx approval |
IECEx UL 16.0051X |
Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.
Thank you for your feedback. In order to leave your feedback, simply fill out the form below.