2-channel signal conditioner
-
24 V DC supply (Power Rail)
The SMART Transmitter Power Supply is designed to provide reliable power and signal conditioning for various applications in hazardous areas. This product is part of a broader family of intrinsic safety barriers that ensure safe operation in environments where explosive gases or dust may be present. By isolating control circuits from the hazardous environment, these barriers protect both equipment and personnel.
Commonly used in industrial automation, process control, and instrumentation, this power supply facilitates the integration of sensors and transmitters into control systems. It operates with a 24 V DC supply and supports two channels, allowing for efficient signal processing and conditioning. Its robust design ensures that it can withstand the rigors of industrial environments while maintaining the necessary safety standards.
|
Load |
0 … 600 andOmega; |
|
Connection |
Power Rail or terminals 14+, 15- |
|
Available voltage |
16 V at 20 mA, terminals 1+, 3 |
|
Output/Output |
functional insulation, rated insulation voltage 50 V AC |
|
Connection |
terminals 1+, 2-, 3; 4+, 5-, 6 |
|
Input signal |
0/4 … 20 mA |
|
Input/power supply |
basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff |
|
Settling time |
200 micro/s |
|
Dimensions |
20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 |
|
Power consumption |
2.6 W at maximum load |
|
Supplementary information |
Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
|
Connection |
terminals 7+, 8-, 9-; 10+, 11-, 12- (sink) terminals 7-, 8+, 9+; 10-, 11+, 12+ (source) see additional information |
|
Signal type |
Analog input |
|
Electromagnetic compatibility |
NE 21:2012 EN 61326-3-2:2008 |
|
Safety Integrity Level (SIL) |
SIL 2 |
|
Connection side |
control side |
|
Connection side |
field side |
|
Output signal |
0/4 … 20 mA (overload > 25 mA) |
|
Ripple |
max. 50 andmicro;A rms |
|
Output/power supply |
functional insulation, rated insulation voltage 50 V AC |
|
Mass |
approx. 150 g |
|
Rated voltage |
18 … 30 V DC |
|
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
|
Protection against electrical shock |
UL 61010-1:2012 |
|
Ripple |
within the supply tolerance |
|
Power dissipation |
1.4 W at maximum load |
|
Display elements |
LED |
|
Rise time/fall time |
100 micro/s |
|
Degree of protection |
IEC 60529:2001 |
|
Optional accessories |
– power feed module KFD2-EB2(.R4A.B)(.SP) – universal power rail UPR-03(-M)(-S) – profile rail K-DUCT-GY(-UPR-03) |
|
Labeling |
space for labeling at the front |
|
Connection |
screw terminals |
|
Deviation |
at 20 °C (68 °F), 0/4 … 20 mA 10 andmicro;A incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
|
External supply (loop) |
2 … 30 V DC |
|
Degree of protection |
IP20 |
|
Ambient temperature |
-20 … 60 °C (-4 … 140 °F) |
|
Input resistance |
max. 265 andOmega; terminals 2-, 3; 5-, 6 , max. 330 andOmega; terminals 1+, 3; 4+, 6 |
|
Frequency range |
field side into the control side: band width with 1 Vpp signal 0 … 7.5 kHz (-3 dB) safe area to hazardous area: band width with 1 VSS signal 0.3 … 7.5 kHz (-3 dB) |
Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.
Thank you for your feedback. In order to leave your feedback, simply fill out the form below.