Pepperl+Fuchs KFD2-UFC-Ex1.D

Frequency Converter with Trip Values
SKU: KFD2-UFC-Ex1.D
0.00

Out of stock

One click request

The Frequency Converter with Trip Values is a 1-channel isolated barrier designed for use with NAMUR sensors and dry contacts. It operates on a 24 V DC supply, making it suitable for various industrial applications that require reliable signal transmission.

All description
Manufacturer: Pepperl+Fuchs
Description:

The Frequency Converter with Trip Values is part of a sophisticated line of intrinsic safety barriers from Pepperl+Fuchs, designed to ensure safe operation in hazardous environments. These barriers are essential for isolating electrical equipment from potentially explosive atmospheres, making them crucial in industries such as oil and gas, chemical processing, and mining.

This device features a single-channel design that allows for the seamless integration of NAMUR sensors or dry contacts, providing a reliable interface for monitoring and controlling processes. The 24 V DC supply via Power Rail enhances its compatibility with existing systems, ensuring efficient power distribution and stable operation.

Common applications for this frequency converter include process automation, where it facilitates the conversion of sensor signals into usable output for further processing or control. By maintaining intrinsic safety standards, these barriers ensure that equipment can operate safely even in the presence of flammable gases or dusts.

Input I

terminals 1+, 3-: Ex ia

Connection

Input I: intrinsically safe: terminals 1+, 3-

Input II: non-intrinsically safe: terminals 13+, 14-

Input II

terminals 13+, 14- non-intrinsically safe

Rated current

approx. 100 mA

Output I, II

signal, relay

Output III/IV

basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff

Connection

output I: terminals 10, 11, 12

output II: terminals 16, 17, 18

outout III: terminasl 19+, 20-

output IV: terminals 8+, 7-

Safety Integrity Level (SIL)

SIL 2

Start-up override/power supply and collective error

functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff

Collective error message

Power Rail

Output IV/power supply and collective error

functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff

Degree of protection

IP20

Power dissipation/power consumption

2 W / 2.2 W

Input

EN 60947-5-6:2000

EU-Type Examination Certificate

TV 99 ATEX 1471

Degree of protection

IEC 60529:2001

Connection

terminals 23+, 24- or power feed module/Power Rail

Mass

300 g

Certificate

TV 02 ATEX 1885 X

Output IV

terminals 8+, 7- non-intrinsically safe

Interface

RS 232

Display elements

LEDs , display

Programming interface

programming socket

Input I

sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact

Mounting

on 35 mm DIN mounting rail acc. to EN 60715:2001

Electromagnetic compatibility

NE 21:2006

Output I, II

terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe

Mutual output I, II, III

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

IECEx approval

IECEx TUN 04.0007

Input II

startup override: 1 … 1000 s, adjustable in steps of 1 s

Interface/power supply and collective error

functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff

Output I, II/other circuits

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output III/power supply and collective error

basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff

Output IV

analog

Signal type

Digital Input

Connection

screw terminals

Ambient temperature

-20 … 60 °C (-4 … 140 °F)

Dimensions

40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3

Input I/other circuits

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Connection side

control side

Connection side

field side

UL approval

E223772

Control elements

Control panel

Output III

electronic output, passive

Rated voltage

20 … 30 V DC

Interface/output III

basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff

Labeling

space for labeling at the front

Supplementary information

Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Output III/start-up override

basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff

Output III

terminals 19+, 20- non-intrinsically safe

Reviews
Leave feedback on the goods

Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.