The Universal Temperature Converter is a 2-channel isolated barrier designed for various temperature measurement applications. It supports thermocouples, RTDs, potentiometers, and voltage inputs, making it versatile for different industrial environments.
The Universal Temperature Converter is part of a comprehensive range of intrinsic safety barriers that are engineered to ensure safe signal transmission in hazardous environments. These devices are particularly crucial in applications where temperature measurement and control are essential, such as in chemical processing, oil and gas exploration, and other potentially explosive atmospheres.
Featuring a 24 V DC supply and the capability to function as a signal splitter, this converter allows for one input to be replicated across two outputs. It supports a variety of input types and provides a configurable current output in both sink and source mode. The integration of line fault detection (LFD) and sensor burnout detection enhances the reliability of the system, while compliance with SIL 2 according to IEC 61508/IEC 61511 standards ensures that it meets stringent safety requirements for industrial applications.
| Output I, II | Analog current output |
| Degree of protection | IEC 60529:2001 |
| Mass | approx. 130 g |
| Connection | terminals 14+, 15- or power feed module/Power Rail |
| Connection | terminals 1, 2, 3; 4, 5, 6 |
| Rated voltage | 20 … 30 V DC |
| Display elements | LEDs |
| Connection | screw terminals |
| Connection side | field side |
| Connection | output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-) output II: terminal 10: source (-), sink (+), terminal 11: source (+), terminal 12: sink(-) |
| Certificate | TV 02 ATEX 1797 X |
| Safety Integrity Level (SIL) | SIL 2 |
| Signal type | Analog input |
| Programming interface | programming socket |
| Electromagnetic compatibility | NE 21:2006 |
| Input resistance | 1 MandOmega; (-100 … 100 mV) |
| Degree of protection | IP20 |
| Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
| Connection side | control side |
| Configuration | via PACTware |
| EU-Type Examination Certificate | CESI 04 ATEX 143 |
| Voltage | selectable within the range -100 … 100 mV |
| Ripple | within the supply tolerance |
| Power dissipation/power consumption | 1.53 W / 1.53 W |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Labeling | space for labeling at the front |
| Potentiometer | 0 … 20 kandOmega; (2-wire connection), 0.8 … 20 kandOmega; (3-wire connection) |
| RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
| Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) |