Pepperl+Fuchs KT-MB-GT2AD.FF

Advanced Diagnostic Gateway
SKU: KT-MB-GT2AD.FF
0.00

Out of stock

One click request

The Advanced Diagnostic Gateway provides a robust system integration solution for Advanced Diagnostics, facilitating seamless communication and management of devices in hazardous environments. With support for both FOUNDATION Fieldbus and PROFIBUS PA, it streamlines the workflow of diagnostic data handling.

All description
Manufacturer: Pepperl+Fuchs
Description:

The Advanced Diagnostic Gateway with Ethernet and FF-H1 Interface is designed to enhance system integration for advanced diagnostic applications in industrial automation. This device acts as a bridge between various fieldbus systems and diagnostic management tools, allowing for efficient data communication and processing. It is particularly suitable for environments classified as Zone 2, ensuring compliance with explosion protection standards.

Common applications include monitoring and managing diagnostic data from field instruments, where it supports integration with Diagnostic Manager or device DTM. The automatic setup of advanced diagnostics simplifies the deployment process, enabling quick configuration and operational readiness. Additionally, the gateway facilitates common alarm handling, ensuring that critical alerts are efficiently managed across the network.

Relative humidity < 95 % non-condensing
Shock resistance EN 60068-2-27
Protocol TCP/IP and UDP/IP
ITK version 6
Degree of protection IP20
Ambient temperature -40 … 60 °C (-40 … 140 °F) hazardous area
-40 … 70 °C (-40 … 158 °F) safe area horizontal DIN rail mounting
LINK/ACT yellow
Housing height see dimensions
Fieldbus standard IEC 61158-2
Certificate TV 14 ATEX 115980 X
Termination integrated
Fieldbus/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Ethernet/Supply functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Housing depth see dimensions
Output II alarm output diagnostic bus channel 2 , volt-free contact , NC contact
Pollution degree max. 2, according to IEC 60664
Electromagnetic compatibility NE 21
Vibration resistance EN 60068-2-6
Number of Diagnostic Bus Channels 2
Rated voltage 9 … 35 V SELV/PELV
Climatic conditions DIN IEC 721
Shock resistance 15 g 11 ms
Galvanic isolation IEC 62103
Rated current 120 … 70 mA
CH1, CH2 yellow: diagnostic bus activity
Transfer rate 100 MBit/s
Connection type RJ-45 socket, 8-pin
Output I, II/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Degree of protection IEC 60529
Diagnostic Bus/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Physical layer profile profile type 114
Port 100 BASE-TX
Polarity polarity-sensitive
Cable length/Channel 30 m
Design / Mounting Motherboard based
Vibration resistance 1 g , 10 … 150 Hz
Firmware update Ethernet
Ethernet/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Output I alarm output diagnostic bus channel 1 , volt-free contact , NC contact
Number of Diagnostic Modules/Channel 31 Using Ethernet Interface , 8 Using Fieldbus Interface
Storage temperature -40 … 85 °C (-40 … 185 °F)
Rated current 0 mA
LED ERR red: Hardware fault
Housing material Polycarbonate
Housing width see dimensions
Fieldbus type FOUNDATION Fieldbus
Output III common alarm , volt-free contact , NC contact
LED PWR green: Power on
IECEx approval IECEx TUN 14.0003X
Rated voltage 19.2 … 35 V DC SELV/PELV
Ethernet IEEE 802.3
Services ICMP , DHCP , AutoIP , HTTP
Power dissipation max. 2.5 W
Mass 470 g
Implementation resource block1x RS
function block4x MDI, 1x MDO, 1x MAI, 1x DI
transducer block16x ADM TB, 1x IO TB
All circuits/FE functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Reviews
Leave feedback on the goods

Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.

Leave feedback

Thank you for your feedback. In order to leave your feedback, simply fill out the form below.

Thank you for your feedback. In order to leave your feedback, simply fill out the form below. “Pepperl+Fuchs KT-MB-GT2AD.FF”

Your email address will not be published. Required fields are marked *

Other products categories