Out of stock
The Advanced Diagnostic Gateway provides a robust system integration solution for Advanced Diagnostics, facilitating seamless communication and management of devices in hazardous environments. With support for both FOUNDATION Fieldbus and PROFIBUS PA, it streamlines the workflow of diagnostic data handling.
The Advanced Diagnostic Gateway with Ethernet and FF-H1 Interface is designed to enhance system integration for advanced diagnostic applications in industrial automation. This device acts as a bridge between various fieldbus systems and diagnostic management tools, allowing for efficient data communication and processing. It is particularly suitable for environments classified as Zone 2, ensuring compliance with explosion protection standards.
Common applications include monitoring and managing diagnostic data from field instruments, where it supports integration with Diagnostic Manager or device DTM. The automatic setup of advanced diagnostics simplifies the deployment process, enabling quick configuration and operational readiness. Additionally, the gateway facilitates common alarm handling, ensuring that critical alerts are efficiently managed across the network.
| Relative humidity | < 95 % non-condensing |
| Shock resistance | EN 60068-2-27 |
| Protocol | TCP/IP and UDP/IP |
| ITK version | 6 |
| Degree of protection | IP20 |
| Ambient temperature | -40 … 60 °C (-40 … 140 °F) hazardous area -40 … 70 °C (-40 … 158 °F) safe area horizontal DIN rail mounting |
| LINK/ACT | yellow |
| Housing height | see dimensions |
| Fieldbus standard | IEC 61158-2 |
| Certificate | TV 14 ATEX 115980 X |
| Termination | integrated |
| Fieldbus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| Ethernet/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| Housing depth | see dimensions |
| Output II | alarm output diagnostic bus channel 2 , volt-free contact , NC contact |
| Pollution degree | max. 2, according to IEC 60664 |
| Electromagnetic compatibility | NE 21 |
| Vibration resistance | EN 60068-2-6 |
| Number of Diagnostic Bus Channels | 2 |
| Rated voltage | 9 … 35 V SELV/PELV |
| Climatic conditions | DIN IEC 721 |
| Shock resistance | 15 g 11 ms |
| Galvanic isolation | IEC 62103 |
| Rated current | 120 … 70 mA |
| CH1, CH2 | yellow: diagnostic bus activity |
| Transfer rate | 100 MBit/s |
| Connection type | RJ-45 socket, 8-pin |
| Output I, II/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff |
| Degree of protection | IEC 60529 |
| Diagnostic Bus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| Physical layer profile | profile type 114 |
| Port | 100 BASE-TX |
| Polarity | polarity-sensitive |
| Cable length/Channel | 30 m |
| Design / Mounting | Motherboard based |
| Vibration resistance | 1 g , 10 … 150 Hz |
| Firmware update | Ethernet |
| Ethernet/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
| Output I | alarm output diagnostic bus channel 1 , volt-free contact , NC contact |
| Number of Diagnostic Modules/Channel | 31 Using Ethernet Interface , 8 Using Fieldbus Interface |
| Storage temperature | -40 … 85 °C (-40 … 185 °F) |
| Rated current | 0 mA |
| LED ERR | red: Hardware fault |
| Housing material | Polycarbonate |
| Housing width | see dimensions |
| Fieldbus type | FOUNDATION Fieldbus |
| Output III | common alarm , volt-free contact , NC contact |
| LED PWR | green: Power on |
| IECEx approval | IECEx TUN 14.0003X |
| Rated voltage | 19.2 … 35 V DC SELV/PELV |
| Ethernet | IEEE 802.3 |
| Services | ICMP , DHCP , AutoIP , HTTP |
| Power dissipation | max. 2.5 W |
| Mass | 470 g |
| Implementation | resource block function block transducer block |
| All circuits/FE | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |