Pepperl+Fuchs LVL-M2

Vibration Limit Switch
SKU: LVL-M2
0.00

Out of stock

One click request

The Vibration Limit Switch is designed for precise monitoring of liquid levels in various industrial applications. It offers a versatile selection of process connections and a variety of electronic modules to ensure compatibility with different process control systems.

All description
Manufacturer: Pepperl+Fuchs
Description:

The Vibration Limit Switch from Pepperl+Fuchs is a critical component in fluid management systems, particularly in applications where reliable level detection is essential. This limit switch operates without mechanically moving parts, resulting in a maintenance-free design that minimizes wear and extends operational life. Its robust construction allows for universal use across a wide range of process connections, making it suitable for diverse industrial environments.

Equipped with advanced monitoring capabilities, the device ensures ongoing functionality by checking for damage to the vibrating fork. Commissioning and maintenance are streamlined through the PROFIBUS PA protocol, facilitating quick integration into existing systems. Additionally, the Vibration Limit Switch meets safety integrity levels up to SIL 2 according to IEC 61508, reinforcing its reliability in critical applications where safety is paramount.

Medium density adjustment on the electronic insert > 0,5 g/cm3 or > 0,7 g/cm3 (other on request)
Display elements electronic inserts:
– electronic inserts FEL50 A (PA), FEL58 (N2): green LED, yellow LED
– electronic inserts FEL51 (AC), FEL52 (E5), FEL54 (WA), FEL55 (SI), FEL56 (N1): green LED, red LED
compact housings:
compact housing with valve connector
– electronic version FEL51 (AC), FEL52 (E5): green LED, red LED
– electronic version FEL58 (N2): green LED, yellow LED
compact housing with M12 x 1 round connector without LEDs
– electronic version FEL52 (E5): green LED, yellow LED, red LED
– electronic version FEL58 (N2): green LED, yellow LED
compact housing with M12 x 1 round connector with LEDs
– electronic version FEL52 (E5): green LED, two yellow LEDs
Ambient temperature -50 … 70 °C (-58 … 158 °F) , function with reduced data values
see section ambient temperature
Designation see technical information (TI)
Non-repeatability 0.1 mm
Measured variable limit level (limit value)
FM approval see control drawings (ZD)
Construction type compact device
Current consumption electronic insert FEL52 (E5): max. 15 mA
Surface quality Ra < 3.2 andmicro;m/80 grit: length, spacer, bushings *A, *B, *E
Vibration resistance EN 60068-2-6
Surge protection electronic insert FEL51 (AC), electronic insert FEL52 (E5), electronic insert FEL54 (WA), electronic insert FEL55 (SI): overvoltage category III
Function test compact housing: function test with test magnet
electronic versions FEL51 (AC), FEL52 (E5) and FEL58 (N2): During the test, the current state of the electronic switch is reversed.
Overspill protection see approval (ZE)
Degree of protection polyester, steel, and aluminum housing: IP66/IP67
compact housing:
– IP65 with valve connector PG11 or 1/2NPT
– IP66/IP68 with M12 x 1 connector without LEDs (1.4435/316L)
– IP69K with M12 x 1 connector with LEDs (1.4435/316L)
Function principle limit detection
Maximum or minimum detection in tanks or pipelines containing all types of liquids including use in explosion hazardous areas. Particularly suited to very aggressive liquids thanks to high degree of corrosion protection.
Measuring method The forks of the sensors vibrate at their intrinsic frequency. This frequency is reduced when covered with liquid.
The change in frequency then activates the limit switch.
Control elements electronic insert FEL50A (PA): 8 switches for device address setting
electronic inserts FEL51 (AC), FEL52 (E5), FEL54 (WA), FEL55 (SI), FEL56 (N1): two switches for fail-safe mode and density change
electronic insert FEL58 (N2): two switches for fail-safe mode and density change and one test button interrupts lead
CSA approval see control drawings (ZD)
Rated voltage electronic insert FEL50A (PA): 9 … 32 V DC
electronic insert FEL51 (AC): 253 V AC, 50/60 Hz
electronic insert FEL52 (E5): 10 … 55 V DC
electronic insert FEL54 (WA): 19 … 253 V AC, 50/60 Hz or 19 … 55 V DC
electronic insert FEL55 (SI): 11 … 36 V DC, PLC
electronic insert FEL56 (N1), FEL58 (N2): isolating amplifier acc. to EN 60947-5-6 (NAMUR)
Influence of medium temperature max. +1.4 … -2.8 mm (-40 … 150 °C (-40 … 302 °F))
Vibration resistance 10 … 50 Hz, 0.15 mm, 100 cycles
Switching delay when fork is covered: approx. 0.5 s, when fork is exposed: approx. 1.0 s (other switching times on request)
additionally configurable for PROFIBUS PA (electronic insert FEL50A (PA)): 0.5 … 60 s
SIL classification up to SIL2 acc. to IEC 61508
Measurement range depends on mounting point
Process connection – cylindrical thread G3/4A, G1A to DIN ISO 228/1 with flat seal to DIN 7603
– conical thread R3/4, R1 to DIN 2999, part 1
– conical thread 3/4NPT, 1NPT to ANSI B 1.20.1
– flush-mounted with welding sleeve to factory standard (G3/4A, G1A)
– Triclamp 1-1/2 inch, 2 inch to ISO 2852
– flanges to EN 1092-1 from DN25, to ANSI B 16.5 from 1 inch, to JIS B 2238 (RF) from DN25
For further information see type code.
Switch behaviour switch-over for minimum/maximum residual current safety on electronic insert
MAX = maximum safety:
The output switches to the power fail response when the fork is covered.
for use with overspill protection for example
MIN = minimum safety:
The output switches to the power fail response when the fork is exposed.
for use with dry running protection for example
When switching on the power supply the output assumes the alarm signal. After max. 2 s it assumes the correct switching mode.
Maximum measured error max. � 1 mm, specified by mounting position
Influence of medium pressure max. 0 … -2.5 mm (-1 … 64 bar)
Power consumption electronic insert FEL52 (E5): max. 0.83 W
electronic insert FEL54 (WA): max. 1.3 W
IECEx approval see instruction manuals (SI)
Mass 600 g , basic weight: compact sensor, electronic insert, stainless steel housing, process connection G2*, additional weight is dependent on housing and process connection
process connections:
– A31 1000 g, A4* 1200 g, A5* 1500 g, A6* 2400 g, A72 4800 g, A81 4900 g, A82 6800 g, A91 7000 g,
A92 11,5 kg, A93 17,3 kg
– – C45 1400 g, C51 1200 g, C71 1600 g, C75 3200 g, C95 5900 g, CA3 5600 g
– D45 1400 g, D51 1200 g, D71 1600 g, D75 3200 g, D95 5900 g, DA3 5600 g
– F45 1400 g, F51 1200 g, F55 2000 g, F61 1400 g, F65 2400 g, F71 1600 g, F75 3200 g, F7F 2600 g,
F81 2400 g, F85 4300 g, F93 4800 g, F95 5900 g, FA3 5600 g, FA5 7500 g
– G3* 200 g
– J13 no information, J16 no information, J17 1700 g, J19 no information, J1A no information, J1C 1700 g
– N3* 200 g, N75 2900 g
– R3* 200 g
– T51 no information, T61 100 g
extension tube, tempeprature spacers, flameproof bushings:
– B* 900 g/m, C* 2300 g/100 inch
– D* 100 g
– J* 900 g/m and 600 g, K* 2300 g/100 inch and 600 g
– L* 700 g
– R* 900 g/m and 700 g, S* 2300 g/100 inch and 700 g
– T* 800 g
Degree of protection IEC 60529
Material wetted parts:
– process connection and extension tube: 1.4435/316L or 2.4610/Alloy C4
– vibration fork: 1.4435/316L or 2.4610/Alloy C4
– flat seal for process connection G2* or G3*: elastomer fibre, asbestos-free
housings:
– polyester housing: PBT-FR with PBT-FR cover or with PA12 cover with sight glass, cover seal: EPDM
– stainless steel housing: 1.4435/316L, cover seal: silicone
– aluminum housing: EN-AC-AlSi10Mg, plastic-coated, cover seal: EPDM
– compact housing with valve connector or M12 connector: 1.4435/316L
cable gland: polyamide or brass, nickel-plated
temperature spacer: 1.4435/316L
flameproof bushing: 1.4435/316L
Dimensions housing: diameter max. 85 mm, height max. 173 mm
temperature separator, flameproof bushing: additional length L 140 mm
process connection: length L 66.5 … 80 mm
extension: length type II, for vertical installation from above same switching point as
Vibracon LVL1, LVL2
vibration fork: width 17.5 mm, fork width 10 mm, length 25 mm
Storage temperature -50 … 80 °C (-58 … 176 °F)
Supplementary documentation technical information (TI)
manuals, brief instructions (BA, KA)
instruction manuals (SI)
control drawings (ZD)
Switching point see section switch point
EU-Type Examination Certificate see instruction manuals (SI)
Electromagnetic compatibility NE 21
Connection electronic inserts: cross section max. 2.5 mm2, lace in end splice in acc. with DIN 46228
ground lead in housing: cross section max. 2.5 mm2
external equipotential bonding: cross section 4 mm2
Influence of medium density max. +4.8 … -3.5 mm (0.5 … 1.5 g/cm3)
Hysteresis approx. 2 mm
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Reference operating conditions ambient temperature: 23 °C (73.4 °F), medium temperature: 23 °C (73.4 °F),
product density: 1 g/cm3 (water), viscosity: 1 mm2/s, medium pressure pe: 0 bar,
sensor mounting: vertical from above, density switch: to > 0.7 g/cm3
Climate class DIN EN 60068-2-38/IEC 68-2-38
Reviews
Leave feedback on the goods

Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.

Leave feedback

Thank you for your feedback. In order to leave your feedback, simply fill out the form below.

Thank you for your feedback. In order to leave your feedback, simply fill out the form below. “Pepperl+Fuchs LVL-M2”

Your email address will not be published. Required fields are marked *

Other products categories