Out of stock
The inductive sensors from Pepperl+Fuchs are designed for non-contact object detection in various industrial applications. These sensors utilize electromagnetic fields to sense metallic objects, offering reliable performance in demanding environments.
Inductive proximity sensors are essential components in automation and control systems, widely used for detecting the presence of metallic objects without physical contact. They operate by generating an oscillating electromagnetic field, which is disrupted when a metal object enters the sensing range. This disruption triggers an output signal, allowing for precise monitoring and control of machinery and processes.
These sensors are particularly beneficial in environments where traditional mechanical switches would be unsuitable due to wear, dirt, or moisture. Common applications include robotics, assembly lines, and packaging machinery, where their durability and reliability enhance operational efficiency. The cylindrical design and flush installation options make them versatile for various mounting configurations, while the brass, nickel-plated housing ensures robust performance in industrial settings.
| General specifications | ||
| Switching element function | DC |
|
| Rated operating distance | 2 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 … 1.62 mm ( -25 … 70 �C (-13 … 158 �F) ) 0 … 1.52 mm ( -40 … -25 �C (-40 … -13 �F) ) |
|
| Reduction factor rAl | 0.18 | |
| Reduction factor rCu | 0.12 | |
| Reduction factor r304 | 0.67 | |
| Nominal ratings | ||
| Operating voltage | 5 … 60 V | |
| Switching frequency | 0 … 1000 Hz | |
| Hysteresis | 1 … 10 typ. 5 % | |
| Reverse polarity protection | reverse polarity tolerant | |
| Short-circuit protection | pulsing | |
| Voltage drop | less than or equal to 5 V | |
| Operating current | 2 … 100 mA | |
| Lowest operating current | 2 mA | |
| Off-state current | 0 … 0.5 mA typ. | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 2250 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| Ambient conditions | ||
| Ambient temperature | -40 … 70 �C (-40 … 158 �F) | |
| Mechanical specifications | ||
| Connection type | Connector M12 x 1 , 4-pin | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP67 | |
Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.
Thank you for your feedback. In order to leave your feedback, simply fill out the form below.