Out of stock
The inductive sensor series features a cylindrical design with a 30 mm housing diameter, constructed from durable PP material. It offers a rated operating distance of 10 mm and utilizes a 2-wire output configuration, making it suitable for various industrial applications.
Inductive proximity sensors are essential components in automation and control systems, designed to detect the presence of metallic objects without direct contact. These sensors operate on the principle of electromagnetic induction, making them highly reliable and effective in a wide range of applications, from manufacturing to packaging and assembly lines.
The cylindrical design of the sensor allows for easy integration into various installations, particularly in flush mount applications. With a robust construction and a rated operating distance of 10 mm, these sensors are capable of precise detection in environments where contact-based sensors may fail. The use of a silicon cable for connection ensures flexibility and durability, catering to diverse industrial needs.
Typical applications for inductive proximity sensors include monitoring the position of machine parts, detecting the presence of tools, and ensuring proper alignment in conveyor systems. Their durability and effectiveness make them a preferred choice in various automation scenarios.
| General specifications | ||
| Switching element function | NAMUR, NC | |
| Rated operating distance | 10 mm | |
| Installation | flush | |
| Output polarity | Safety Function | |
| Assured operating distance | 0 … 8.1 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.3 | |
| Reduction factor r304 | 0.85 | |
| Safety Integrity Level (SIL) | up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the exida Functional Safety Assessment document which is available on www.PEPPERL+FUCHS.com as an integral part of this product’s documentation. |
|
| Nominal ratings | ||
| Nominal voltage | 8 V DC | |
| Switching frequency | 0 … 300 Hz | |
| Current consumption | ||
| Measuring plate not detected | greater or equal 3 mA | |
| Measuring plate detected | less than or equal to 1 mA | |
| Functional safety related parameters | ||
| MTTFd | 9190 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
| Approvals and certificates | ||
| FM approval | ||
| Control drawing | 116-0165F | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated less than or equal to 36 V | |
| Ambient conditions | ||
| Ambient temperature | -50 … 100 °C (-58 … 212 °F) | |
| Mechanical specifications | ||
| Connection type | cable silicone , 2 m | |
| Core cross-section | 0.75 mm2 | |
| Housing material | PP | |
| Sensing face | PP | |
| Housing diameter | 30 mm | |
| Degree of protection | IP68 | |
| Note | Security relevant only up to -40°C | |
| General information | ||
| Use in the hazardous area | see instruction manuals | |
| Category | 1G- 2G- 1D | |
Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.
Thank you for your feedback. In order to leave your feedback, simply fill out the form below.