The Inductive sensor is a cylindrical type sensor with a housing diameter of 18 mm, designed for reliable proximity detection. Featuring a rated operating distance of 8 mm, this sensor operates with a DC voltage and is equipped with a 2-wire output type.
Inductive proximity sensors are widely utilized in automation and industrial applications for non-contact detection of metallic objects. These sensors function by generating an electromagnetic field and detecting changes in this field when a conductive object enters the sensing range. The cylindrical design and robust construction of these sensors make them suitable for various environments, including those with limited space.
Common applications for inductive sensors include position sensing on conveyor systems, metal part detection in manufacturing processes, and automation in assembly lines. Their ability to function effectively in harsh conditions, combined with features such as a silicone cable connection and ATEX compliance for hazardous environments, ensures reliable operation across a range of industries.
| General specifications | ||
| Switching element function | NAMUR, NC | |
| Rated operating distance | 8 mm | |
| Installation | non-flush | |
| Output polarity | Safety Function | |
| Assured operating distance | 0 … 6.48 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.3 | |
| Reduction factor r304 | 0.85 | |
| Safety Integrity Level (SIL) | up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the exida Functional Safety Assessment document which is available on www.PEPPERL+FUCHS.com as an integral part of this product’s documentation. |
|
| Nominal ratings | ||
| Nominal voltage | 8 V | |
| Operating voltage | 5 … 25 V 1) | |
| Switching frequency | 0 … 200 Hz | |
| Current consumption | ||
| Measuring plate not detected | min. 3 mA | |
| Measuring plate detected | less than or equal to 1 mA | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated less than or equal to 36 V | |
| Ambient conditions | ||
| Ambient temperature | -40 … 100 �C (-40 … 212 �F) | |
| Mechanical specifications | ||
| Connection type | cable silicone , 10 m | |
| Core cross-section | 0.75 mm2 | |
| Housing material | Hostalen PPN, black | |
| Sensing face | Hostalen PPN, black | |
| Housing diameter | 18 mm | |
| Degree of protection | IP68 | |
| General information | ||
| Use in the hazardous area | see instruction manuals | |
| Category | 1G- 2G- 3G- 1D- 3D | |