Pepperl+Fuchs VAA-2E-PM-S

AS-Interface EMERGENCY STOP button
SKU: VAA-2E-PM-S
0.00

Out of stock

One click request

The AS-Interface EMERGENCY STOP button is a critical safety component designed for industrial applications. It features a 2-channel configuration with compelled connections and is overload-protected in compliance with IEC 60947-5-5.

All description
Manufacturer: Pepperl+Fuchs
Description:

The AS-Interface EMERGENCY STOP button is engineered for safety applications in industrial environments, ensuring reliable emergency stop functionality. This device is particularly suited for use in automated systems where safety and compliance with industry standards are paramount. The button’s biased actuator allows for self-monitoring, providing an additional layer of safety by ensuring that the system can detect any faults or malfunctions.

Featuring TV-approval for system components, this emergency stop button is designed to meet rigorous safety standards, making it an ideal choice for various industrial settings, including manufacturing, material handling, and process automation. The unlocking mechanism, which can be activated by turning or pulling, ensures that operators can quickly and effectively reset the system after an emergency stop, enhancing overall operational efficiency.

ID code B
MTTFd 200 a
Functional safety EN 62061:2005
EN 61508 Parts 1-7:2010
NFPA 79:2007
EN 60204-1:2006
Installation Installation in 22 mm hole
ID1 code F
Relative humidity 40 … 85 % , noncondensing
Connection Crimp terminal sockets (JST)
1.5 m Connecting cable with crimp on 2 flexible leads supplied with delivery
AS-Interface specification V2.1
Mass 105 g
Ambient temperature -25 … 55 °C (-13 … 131 °F) (no freezing)
Degree of protection EN 60529:2000
Operating force Push: 32 N
Pull: 21 N
Turn: 0.27 Nm
Minimum for positive opening operation: 60 Nm
Rated operating voltage 26.5 … 31.6 V from AS-Interface
Life span > 250,000 switching operations
AS-Interface EN 62026-2:2013
Number/Type 2 NC
Safety function by positive opening
in accordance with IEC/EN 60947-5-1
Reset by pulling
Insulation resistance min. 100 MandOmega;
Data bits (function via AS-Interface) input output
Required master specification V2.0
Protection class III
ID2 code E
Parameter bits (programmable via AS-i) function
B10d 1 E+5
Storage temperature -40 … 70 °C (-40 … 158 °F)
Operating distance for positive opening operation: min. 4 mm
maximal: 4.5 mm
Degree of protection IP65
Slave type Safety-Slave
IO code 0
Electrical safety EN 60947-5-5:1997+A1:2005
Rated operating current 25 mA
UL File Number E198304
Profile S-0.B.E
Supply from AS-Interface
Electromagnetic compatibility EN 62026-2:2013
Reviews
Leave feedback on the goods

Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.

Leave feedback

Thank you for your feedback. In order to leave your feedback, simply fill out the form below.

Thank you for your feedback. In order to leave your feedback, simply fill out the form below. “Pepperl+Fuchs VAA-2E-PM-S”

Your email address will not be published. Required fields are marked *

Other products categories