Out of stock
The AS-Interface EMERGENCY STOP button is a critical safety device designed for industrial applications, featuring a dual-channel configuration that ensures reliable operation. Its integrated illumination enhances visibility, while the compliance with IEC 60947-5-5 guarantees overload protection.
The AS-Interface EMERGENCY STOP button is an essential component in safety-critical environments, providing an effective means of halting machinery and processes swiftly in emergencies. This product is engineered to meet stringent safety standards, making it suitable for a variety of industrial applications, including manufacturing, automation, and material handling. The dual-channel setup ensures redundancy, which is vital for maintaining operational integrity during fault conditions.
Designed for ease of use, the EMERGENCY STOP button features a biased actuator that allows for self-monitoring, enhancing the reliability of emergency interventions. The unlocking mechanism, achieved through turning or pulling, adds a layer of safety and functionality, ensuring that the device can be reset effectively after activation. Furthermore, the integration of illumination in the actuator provides visual cues, promoting immediate recognition in high-stress situations.
| ID1 code | F |
| MTTFd | 200 a |
| Rated operating voltage | 26.5 … 31.6 V from AS-Interface |
| Profile | S-7.B.E. |
| Connection | Crimp terminal sockets (JST) 1.5 m Connecting cable with crimp on 2 flexible leads supplied with delivery |
| Installation | Installation in 22 mm hole |
| Rated operating current | 40 mA |
| Protection class | III |
| Relative humidity | 40 … 85 % , noncondensing |
| Data bits (function via AS-Interface) | |
| ID code | B |
| Life span | > 250,000 switching operations |
| Insulation resistance | min. 100 MandOmega; |
| Mass | 105 g |
| Ambient temperature | -25 … 55 °C (-13 … 131 °F) (no freezing) |
| Functional safety | EN 62061:2005 EN 61508 Parts 1-7:2010 NFPA 79:2007 EN 60204-1:2006 |
| Number/Type | 2 NC Safety function by positive opening in accordance with IEC/EN 60947-5-1 Reset by pulling |
| Number/Type | LED red |
| Required master specification | V2.0 |
| UL File Number | E198304 |
| Slave type | Safety-Slave |
| Electrical safety | EN 60947-5-5:1997+A1:2005 |
| Degree of protection | EN 60529:2000 |
| IO code | 7 |
| Degree of protection | IP65 |
| AS-Interface | EN 62026-2:2013 |
| Supply | from AS-Interface |
| Supply | from AS-Interface |
| Parameter bits (programmable via AS-i) | function |
| Operating force | Push: 32 N Pull: 21 N Turn: 0.27 Nm Minimum for positive opening operation: 60 Nm |
| Storage temperature | -40 … 70 °C (-40 … 158 °F) |
| AS-Interface specification | V2.1 |
| Electromagnetic compatibility | EN 62026-2:2013 |
| Operating distance | for positive opening operation: min. 4 mm maximal: 4.5 mm |
| ID2 code | E |
| B10d | 1 E+5 |
Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.
Thank you for your feedback. In order to leave your feedback, simply fill out the form below.