Out of stock
The AS-Interface sensor module serves as an A/B slave, enabling extended addressing capabilities for connecting up to 62 slaves in a single network. Its robust construction features a one-piece housing with a stainless steel base, designed for both durability and ease of installation.
The AS-Interface sensor module is an integral component in industrial automation, facilitating communication between sensors and control systems. This device is particularly suited for environments requiring the connection of multiple sensors, as it supports 2-, 3-, and 4-wire sensor inputs while maintaining effective communication monitoring. The module is designed for DIN rail mounting, ensuring a secure and organized integration into existing control cabinets.
Featuring innovative SPEEDCON technology with metal threaded inserts, the sensor module allows for tool-free installation, streamlining the setup process. The flat cable connection employs cable piercing techniques, which not only simplifies wiring but also accommodates a variable flat cable guide for enhanced flexibility in installation. This makes it suitable for various industrial applications where reliable sensor communication is essential, including manufacturing, process control, and machinery automation.
| UL File Number | E223772 |
| Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC |
| Rated operating current | 40 mA (without sensors) / max. 240 mA |
| Fieldbus standard | EN 62026-2:2013 |
| Supply | from AS-Interface |
| Signal delay | < 1 ms (input/AS-Interface) |
| MTTFd | 410 a |
| AS-Interface specification | V3.0 |
| Altitude | 2000 m above MSL |
| Degree of protection | IP67 |
| Profile | S-0.A.2 |
| Rated operating voltage | 26.5 … 31.6 V from AS-Interface |
| Input current | 8 mA (limited internally) |
| ID1 code | 7 |
| Vibration resistance | 0.75 mm 10 … 57 Hz , 5 g 57 … 150 Hz, 20 cycles |
| Relative humidity | 85 % , noncondensing |
| Noise immunity | EN 61000-6-2:2005 EN 62026-2:2013 |
| Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral |
| Mission Time (TM) | 20 a |
| Pollution degree | 3 |
| Shock and impact resistance | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
| Parameter bits (programmable via AS-i) | function |
| Degree of protection | EN 60529:2000 |
| Emitted interference | EN 61000-6-4:2007 |
| LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
| Data bits (function via AS-Interface) | |
| LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor supply |
| Switching point | according to DIN EN 61131-2 (Type 2) |
| Mass | 200 g |
| ID code | A |
| Connection | cable piercing method flat cable yellow inputs: M12 round connector |
| ID2 code | 2 |
| Current loading capacity | 200 mA, overload and short-circuit protected |
| LED IN | switching state (input); 4 LED yellow |
| Required master specification | V2.1 |
| Protection class | III |
| Input | EN 61131-2 |
| AS-Interface | EN 62026-2:2013 |
| IO code | 0 |
| Slave type | A/B slave |
| Mounting | Mounting plate |
| Diagnostic Coverage (DC) | 0 % |
| Storage temperature | -25 … 85 °C (-13 … 185 °F) |
| Ambient temperature | -25 … 70 °C (-13 … 158 °F) |
| Voltage | 21 … 31 V |
| Climatic conditions | For indoor use only |
| Tightening torque, cable gland | 0.4 Nm |
Currently, the goods have no revocation.
Your feedback will be the first to
Share your thoughts, your opinion about the product.
Thank you for your feedback. In order to leave your feedback, simply fill out the form below.