The AS-Interface gateway is designed to facilitate seamless communication between AS-Interface networks and PROFINET IO systems, adhering to the AS-Interface specification 3.0. It features advanced diagnostic capabilities and user-friendly commissioning processes.
The AS-Interface gateway serves as a critical component in industrial automation, linking AS-Interface networks to higher-level PROFINET IO systems. This device is compliant with the AS-Interface specification 3.0, ensuring reliable communication and integration in various applications, such as factory automation, process control, and building management systems. The gateway offers comprehensive connectivity options, allowing all AS-Interface functions to be executed via Ethernet.
Equipped with a graphic display for easy commissioning and fault diagnosis, the gateway provides real-time feedback through visual indicators, including LEDs. Users can monitor AS-Interface performance and detect issues such as duplicate addressing, earth faults, and noise interference. With local commissioning capabilities or the option to use AS-i Control Tools software, the gateway ensures efficient setup and maintenance of AS-Interface networks, making it an essential tool for system integrators and maintenance engineers in industrial environments.
| AS-Interface | EN 62026-2:2013 |
| AS-Interface | removable spring clamp terminals |
| LED AS-i ACTIVE | AS-Interface operation normal; LED green |
| Degree of protection | EN 60529:2000 |
| Interface type | PROFINET I / O device (IRT) |
| Rated operating current | 300 mA from AS-Interface |
| Display | Illuminated graphical LC display for addressing and error messages |
| Insulation voltage | 500 V |
| Switch SET | Selection and setting of a slave address |
| Button MODE | Mode selection PRJ-operation/save configuration/cursor |
| EMC monitoring | integrated |
| AS-Interface specification | V3.0 |
| LED CONFIG ERR | configuration error; LED red |
| Duplicate address detection | from AS-Interface slaves |
| Interface type | RS 232, serial Diagnostic Interface |
| LED ETHERNET | ethernet active; LED green |
| Mass | 500 g |
| Storage temperature | -25 … 85 °C (-13 … 185 °F) |
| Diagnostics function | Extended function via display |
| Ambient temperature | 0 … 55 °C (32 … 131 °F) |
| LED PRJ MODE | projecting mode active; LED yellow |
| Transfer rate | 10 MBit/s / 100 MBit/s , Automatic baud rate detection |
| LED POWER | voltage ON; LED green |
| Interface type | Chip card slot |
| MTTFd | 105 a at 30 °C |
| Earth fault detection | integrated |
| OK button | Mode selection traditional-graphical/confirmation |
| LED U AS-i | AS-Interface voltage; LED green |
| EAC conformity | TR CU 020/2011 |
| Rated operating voltage | from AS-Interface |
| Construction type | Low profile housing , Stainless steel |
| LED PRG ENABLE | autom. programming; LED green |
| PROFINET | RJ-45 |
| ESC button | Mode selection traditional-graphical/cancel |
| Standards | EN 61000-6-2:2005, EN 61000-6-4:2007 |
| UL File Number | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source |
| Transfer rate | 19,2 kBit/s |
| UL approval | An isolated source with a secondary open circuit voltage of 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device. |
| Degree of protection | IP20 |
| Protocol | Media Redundancy Protocol (MRP) |
| Electromagnetic compatibility | EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Physical | 2 x RJ-45 |